Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 5383 Click

主站蜘蛛池模板: 色偷偷成人网免费视频男人的天堂 | 欧美亚洲国产精品久久第一页| 91精品国产综合久久精品| 亚洲精品第一国产综合野| 欧美日韩国产网站| 一边摸一边爽一边叫床视频| 公与2个熄乱理在线播放| 天堂网在线观看| 欧美VA久久久噜噜噜久久| 蜜桃麻豆WWW久久囤产精品| 中文字幕亚洲乱码熟女一区二区| 农村野战videossexjyzz| 夜夜爽免费888视频| 欧美乱妇高清视频免欢看关| 麻豆69堂免费视频| 一本无码人妻在中文字幕免费| 免费a级黄色片| 国产精品视频免费一区二区| 日韩不卡视频在线| 97精品依人久久久大香线蕉97 | 国产精品成人无码久久久久久| 最近中文字幕无| 精品国产不卡在线电影| 69影院毛片免费观看视频在线| 久久精品一区二区东京热| 免费黄色在线网址| 国产欧美亚洲精品a第一页 | 色台湾色综合网站| 91在线精品亚洲一区二区| 久久9精品久久久| 亚洲黄色a级片| 天堂中文在线资源| 日本精品啪啪一区二区三区| 男女性接交无遮挡免费看视频| 精品国产无限资源免费观看| JZZIJZZIJ日本成熟少妇| 久久久久人妻一区精品| 亚洲永久中文字幕在线| 国产欧美日韩综合| 女人让男生桶的视频免费| 清纯秘书被总经理吸乳小说|