Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 5210 Click

主站蜘蛛池模板: 天堂8在线天堂bt| 永久免费无码网站在线观看个 | 黄网在线观看免费| 橘梨纱视频一区二区在线观看| 快一点使劲c我在线观看| 四虎免费影院ww4164h| 亚洲av本道一区二区三区四区 | freeⅹxx69性欧美按摩| 精品久久久久中文字幕一区| 少妇一晚三次一区二区三区| 国产成人免费网站在线观看| 亚洲综合伊人久久大杳蕉| 99精品无人区乱码在线观看| 羞耻暴露办公室调教play视频| 成年日韩片av在线网站| 又紧又大又爽精品一区二区 | 999国产精品999久久久久久| 波多野结衣无内裤护士| 成人看片黄在线观看| 又粗又长又硬太爽了视频快来| 三级日本高清完整版热播| 韩国精品视频在线观看| 欧美成aⅴ人高清免费观看| 国产精品久久久久久久久久免费 | 亚洲免费网站观看视频| a级毛片在线观看| 精品国产综合区久久久久久| 妖精色AV无码国产在线看| 可以免费观看的一级毛片| 两个人看的www高清免费视频| 精品久久中文字幕有码| 国语自产偷拍精品视频偷拍| 免费在线观看日韩| 99在线精品免费视频| 男女真实无遮挡xx00动态图120秒 男女肉粗暴进来120秒动态图 | 国产一区在线mmai| 欧美精品在线视频| 国产男女猛烈无遮挡免费视频 | 香蕉视频免费在线播放| 校服白袜男生被捆绑微博新闻| 国产又黄又爽胸又大免费视频|